Voltage drop calculator: cable drop and minimum wire size

Drop in volts and percent for a copper or aluminium cable, and the minimum cross-section in mm² to stay within your limit (NF C 15-100 method). Free.

  • Instant result
  • Formula and standards shown
  • On desktop and phone

Pre-filled example

A 35 mm², 110 m copper cable supplying a 140 A load on 400 V three-phase, power factor 0.8.

m
A
mΩ/m
V
mm²
More options (2)
Ω·mm²/m
%

Result

8.84VVoltage drop ΔU

Relative voltage drop
3.84%
  • Caution : Cable ampacity Iz and protection are not checked here.
  • Caution : Beyond 100 m, NF C 15-100 allows 0.005 % more per metre, up to 0.5 %.

Free during the beta, no credit card

Does not replace the installation design or its check by a qualified person.

What is voltage drop?

Voltage drop is the loss of voltage along a cable, between the origin of the circuit and the load, caused by the resistance and reactance of the conductors carrying the current. It grows with length and current, falls as the cross-section increases, and is given in volts or as a percentage of the nominal voltage. IEC 60364-5-52 (Annex G) and its national versions, BS 7671 in the UK or NF C 15-100 in France, set limits for low-voltage installations, while the US National Electrical Code recommends values in informational notes.

A maintenance team usually meets excessive voltage drop as a symptom rather than on a drawing: a motor that struggles to start or runs hot, contactors that chatter, a drive that trips on undervoltage. The risk is highest when a machine moves to the far end of the workshop or a load is added to an existing feeder, because the cable was sized for the situation before.

Reference documents : IEC 60364-5-52, Annex G (Table G.52.1) ; BS 7671, Appendix 4 ; NFPA 70 (NEC), sections 90.5(C), 210.19 and 215.2

Voltage drop results filed with the wiring change

Here, the calculator is free and the result is gone when you close the page. In Reglova, it is attached to the work order on the right machine: you find it again at the next breakdown, and on audit day.

The CMMS software comparison, our gaps included
  • Attached to the work order with its inputs: the server recalculates it, it stays verifiable.
  • On the technician's phone, even without a network.
  • In the machine's history, for the next breakdown.
  • The asset's nameplate data pre-fills the calculation.
Reglova · Calculations · Work order WO-AT01-04219
Silent video, 33 s: from the work order for an oil leak on a shear cylinder, the tightening torque of an M12 bolt, then "Attach to the work order". A step to tighten it to 93.1 N·m lands in the checklist (step text from the French demo data). Watch the video

When to calculate cable voltage drop

  1. 01

    Check the supply of a machine added at the far end of the workshop.

  2. 02

    Explain a motor that struggles to start at the end of a long run.

  3. 03

    Prepare a wiring change with the design office or the electrician.

Good to know

The current-carrying capacity Iz and the cable protection are not checked here, and the permitted drop depends on your country's wiring rules. The calculation replaces neither the installation design nor its inspection by a qualified person.

Voltage drop formula and minimum cross-section

The calculator applies the formula of the French wiring standard NF C 15-100 and its guide UTE C 15-105, ΔU = b·(ρ1·L/S·cos φ + λ·L·sin φ)·IB. It gives the drop in volts and as a percentage for the cross-section entered and, if you set a limit, the calculated minimum cross-section and the standard size to choose.

Formula · Reference documents

ΔU = b·(ρ1·L/S·cos φ + λ·L·sin φ)·IB, b = 1 three-phase, 2 single-phase ; ΔU % = 100·ΔU/U0 ; Smin = b·ρ1·L·cos φ·IB / (ΔUmax − b·λ·L·sin φ·IB)

NF C 15-100, UTE C 15-105 ; ρ1 copper 0.023, aluminium 0.037 Ω·mm²/m (Eduscol)

Inputs and accepted ranges
InputUnitAccepted rangeExample
Supply2 optionsThree-phase
Cable lengthm0.1 to 10,000110 m
Design current IBA0.01 to 10,000140 A
Power factor cos φ0.01 to 10.8
Conductor2 optionsCopper
Resistivity ρ1 (otherwise from conductor)Ω·mm²/m0.01 to 0.1Optional
Reactance per length λmΩ/m0 to 10.08 mΩ/m
Phase-to-neutral voltage U0V1 to 1,000230 V
Cross-sectionmm²0.5 to 1,00035 mm²
Permitted drop%0.1 to 20Optional
Calculated results
  • Voltage drop ΔUV
  • Relative voltage drop%
  • Standard cross-sectionmm²
  • Minimum cross-sectionmm²
  • Drop with that cross-section%
What the calculator flags
  • Cable ampacity Iz and protection are not checked here.
  • The drop exceeds the permitted limit.
  • Beyond 100 m, NF C 15-100 allows 0.005 % more per metre, up to 0.5 %.